Action on Loss of Pressure

1 min read

No internal source of release #

The over-pressure within the enclosure is monitored by a pressure switch/sensor, and a flow-rate switch/sensor, located at the exhaust dust, is used to monitor the rate of flow of the safe gas through the enclosure. Loss of over-pressure or rate of flow will activate either an alarm or shutdown of the internal electrical components, the action taken being dependent on:

  1. The EPL requirement of the area in which the system is located;
  2. The type of equipment/components within the enclosure.

IEC 60079-14:2013, Table 18, specifies the action to be taken on loss of pressure as follows:

EPL requirementEnclosure contains equipment not meeting EPL ‘Gc’ requirements without pressurisationEnclosure contains equipment meeting EPL ‘Gc’ requirements without pressurisation
‘Gb’Alarm and switch off aAlarm b
‘Gc’Alarm bNo action

a – If automatic switch-off would introduce a more dangerous condition, other precautionary measures should be taken, for example, duplication of protective gas supply.

b – If the alarm operates, immediate action should be taken to restore the integrity of the system.

With an internal source of release #

The action to be taken depends on the Zone, type of equipment and the type/severity of the release. (Details are beyond the scope of these notes).